Ecostar oil burners.
Burners for heavy and light fuel oil for boilers and furnaces. Oil preheater, fuel pump, one-stage, two-stage and modulating operation. Heavy oil from 90 kW to 11.5 MW.
An oil burner works well wherever there is no gas connection, or where independence from a gas supplier is needed. It does, however, call for careful adjustment and regular servicing of the nozzles, pumps and electrodes.
How a heavy-oil burner works
Heavy fuel oil is too viscous to atomise at ambient temperature. In ECO burners, an electric preheater raises the oil to up to 135 °C, a pump raises the pressure to 18–25 bar, and the fuel is mechanically atomised at the nozzle. Thermostats monitor the oil temperature, and solenoid valves cut off the fuel supply without dripping.
Equipment of ECO oil burners (per the manufacturer's catalogue)
- Air-damper servo motor — simultaneous damper movement and precise air control.
- IP56-rated control panel for operation in demanding conditions.
- Adjustable mounting flange making it easier to fit the burner to the boiler.
- Lightweight aluminium fan housing and an air-intake design that reduces noise.
In modulating models the manufacturer uses a return-oil control valve in the lance, giving a wide power-turndown range with good atomisation.
Heavy oil — ECO burner power ranges
One-stage operation (C1)
| Model | Moc [kW] | Oil consumption [kg/h] |
|---|---|---|
| ECO 2 O(S) C1 | 90–168 | 8–15 |
| ECO 2 O(S) C1a | 112–292 | 10–26 |
| ECO 30 O(S) C1 | 112–404 | 10–36 |
| ECO 30 O(S) C1a | 112–561 | 10–50 |
| ECO 45 O(S) C1 | 202–651 | 18–58 |
| ECO 45 O(S) C1a | 202–898 | 18–80 |
| ECO 45 O(S) C1b | 281–1 010 | 25–90 |
Two-stage operation (C2)
| Model | Moc [kW] | Oil consumption [kg/h] |
|---|---|---|
| ECO 30 O(S) C2 | 112–449 | 10–40 |
| ECO 30 O(S) C2a | 112–729 | 10–65 |
| ECO 45 O(S) C2 | 202–752 | 18–67 |
| ECO 45 O(S) C2b | 247–1 180 | 22–105 |
| ECO 50 O(S) C2 | 393–1 571 | 35–140 |
| ECO 55 O(S) C2 | 449–2 020 | 40–180 |
| ECO 55 O(S) C2a | 449–2 469 | 40–220 |
| ECO 60 O(S) C2 | 696–3 000 | 62–267 |
| ECO 65 O(S) C2 | 853–3 500 | 76–312 |
| ECO 70 O(S) C2 | 1 066–4 070 | 95–363 |
Modulating operation (C3)
| Model | Moc [kW] | Oil consumption [kg/h] |
|---|---|---|
| ECO 45 O(S) C3b | 247–1 180 | 22–105 |
| ECO 50 O(S) C3 | 393–1 571 | 35–140 |
| ECO 55 O(S) C3 | 449–2 020 | 40–180 |
| ECO 55 O(S) C3a | 449–2 469 | 40–220 |
| ECO 60 O(S) C3 | 700–3 000 | 62–267 |
| ECO 65 O(S) C3 | 850–3 500 | 76–312 |
| ECO 70 O(S) C3 | 1 067–4 070 | 95–363 |
| ECO 75 O(S) C3 | 1 167–5 600 | 104–500 |
| ECO 8 O(S) C3 | 1 167–5 600 | 104–500 |
| ECO 8 O(S) C3a | 1 872–6 165 | 167–550 |
| ECO 8 O(S) C3b | 2 049–6 700 | 183–600 |
| ECO 9 O(S) C3 | 3 558–11 500 | 317–1 025 |
Data per the Ecostar catalogue for heavy-oil burners (oil consumption per the manufacturer). The figures are indicative; we confirm the final data in the quotation. The manufacturer states CO emissions below 125 mg/kWh and NOx below 250 mg/kWh at an excess-air ratio of 1.2–1.3.
Light fuel oil
Light-oil burners are available in the ECO 1–30 series (from a dozen or so to several hundred kilowatts) and in FPB process burners. Below are the ranges of FPB process burners for light oil (diesel).
| Model | Praca | Moc [kW] | Max. oil consumption [kg/h] |
|---|---|---|---|
| FPB 200 L1 | 1-stage | 47–233 | 19,6 |
| FPB 300 L1 | 1-stage | 70–349 | 29,4 |
| FPB 400 L1 | 1-stage | 93–465 | 39,2 |
| FPB 400 L2 | 2-stage | 93–465 | 39,2 |
| FPB 550 L2 | 2-stage | 128–640 | 53,9 |
| FPB 870 L2 | 2-stage | 202–1 012 | 85,3 |
| FPB 1200 L2 | 2-stage | 279–1 395 | 117,6 |
| FPB 1600 L2 | 2-stage | 372–1 860 | 156,9 |
| FPB 2000 L2 | 2-stage | 465–2 326 | 196,1 |
| FPB 2500 L2 | 2-stage | 581–2 907 | 245,1 |
| FPB 550 L3 | modulating | 128–640 | 53,9 |
| FPB 870 L3 | modulating | 202–1 012 | 85,3 |
| FPB 1200 L3 | modulating | 279–1 395 | 117,6 |
| FPB 1600 L3 | modulating | 372–1 860 | 156,9 |
| FPB 2000 L3 | modulating | 465–2 326 | 196,1 |
| FPB 2500 L3 | modulating | 581–2 907 | 245,1 |
| FPB 3500 L3 | modulating | 814–4 070 | 343,1 |
| FPB 5000 L3 | modulating | 1 163–5 814 | 490,2 |
Send us the data from the boiler or furnace nameplate — we will size the burner.
Power, fuel, combustion chamber pressure. We reply within 48 hours, with no obligation.